1. Ambient Temperature:-40℃~+40℃
2. Mounting Height:≤1000m (Altitude)
3. Relative humidity around: daily average 95%, monthly average w90%;
4. Surrounding air: not applicable to places with corrosion, serious pollution, combustible gas and violent vibration;
5. If an earthquake occurs, the earthquake intensity shall not exceed magnitude 8.Structural features
Main technical parameters
Project | Unit | Parameters | |
Rated voltage | KV | 40.5 | |
Rated insulation level | Lightning impulse withstand voltage (full wave) | KV | 185 |
Power frequency withstand voltage (1min) | 95 | ||
Rated frequency | HZ | 50 | |
Rated current | A | 630;1250;1600;2000 | |
Rated short circuit breaking time | Power frequency withstand voltage (1min) | KV | 20、25、31.5 |
Rated sh or t-circuit making current (peak) | KV | 50、63、80 | |
Rated dynamic stability current (peak) | KV | 50、63、80 | |
4S thermal stability current (effective value) | KV | 20、25、31.5 | |
Enclosure protection class | Vacuum circuit breaker cabinet | MM | IP4X |
Overall dimension (width× deep× High) | SF6 circuit breaker cabinet | 1400×2200×2600 | |
Circuit breaker technical parameter
High |
| 2650 |
Width | Rated current 1600A and above | 1400 |
Deep | Lower cable inlet and outlet | 2870 |
Overhead incoming and outgoing lines | 2950 |
Circuit breaker technical parameter
Project | Unit | Parameters | ||
Rated voltage | KV | 40.5 | ||
Rated insulation level | Lightning impulse withstand voltage (full wave) | KV | 185 | |
Power frequency withstand voltage (1min) | 95 | |||
Rated frequency | HZ | 50 | ||
Rated current | A | 1250;1600;2000 | 630;1250;1600;2000 | |
Rated sh or t circuit breaking time | KV | 20、25、31.5 | 20、25、31.5 | |
Rated sh or t-circuit making current (peak) | KV | 50、63、80 | 63、80 | |
Rated dynamic stability current (peak) | KV | 50、63、80 | 63、80 | |
4S thermal stability current (effective value) | KV | 20、25、31.5 | 25、31.5(3s) | |
Opening time | ms | 36~60 | ≤ 45 | |
Closing time | ms | 40~90 | ≤ 75 | |
Rated operating sequence |
| Off-0.3s-On-Off-180S-On-Off | ||

Scheme number | 01 | 02 | 03 | 04 | 05 | ||
Main circuit scheme diagram | | | | | | ||
| Vacuum circuit breaker ZN85-40.5 | 1 | 1 | 1 | 1 | 1 | |
| Current transformer LDJ5-35 |
| 3 | 3 | 6 |
| |
| Voltage transformer JDJ9-35 |
|
|
|
|
| |
| Lightning arrester HY5WZ | 0 or 3to select | 0 or 3to select | 0 or 3to select | 0 or 3to select | 0 or 3to select | |
| Grounding switch JN12-35 | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | |
| Live display | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | |
| Fuse XRNP-35 |
|
|
|
|
| |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Cable incoming (outgoing) line | ||
Scheme number | 06 | 07 | 08 | 09 | 10 | ||
Main circuit scheme diagram | | | |
|
| ||
| Vacuum circuit breaker ZN85-40.5 | 1 | 1 | 1 | 1 | 1 | |
| Current transformer LDJ5-35 | 1~3 | 1~3 | 4~6 |
| 1~3 | |
| Voltage transformer JDJ9-35 |
|
|
|
|
| |
| Lightning arrester HY5WZ | 0 or 3to select | 0 or 3to select | 0 or 3to select |
|
| |
| Grounding switchJN12-35 | 0 or 1to select | 0 or 1to select | 0 or 1to select |
|
| |
| Live display | 0 or 1to select | 0 or 1to select | 0 or 1to select |
|
| |
| Fuse XRNP-35 |
|
|
|
|
| |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Cable incoming (outgoing) line | Cable incoming (outgoing) line | Cable incoming (outgoing) line | Left (right) contact | Left (right) contact | ||
Scheme number | 11 | 12 | 13 | 14 | 15 | |||
Main circuit scheme diagram | | | | | | |||
| Vacuum circuit breaker ZN85-40.5 | 1 | 1 | 1 | 1 | 1 | ||
| Current transformer LDJ5-35 | 1~3 | 4~6 |
| 1~3 |
| ||
| Voltage transformer JDJ9-35 |
|
|
|
|
| ||
| Lightning arrester HY5WZ |
|
|
|
|
| ||
| Grounding switchJN12-35 |
|
|
|
|
| ||
| Live display |
|
|
|
|
| ||
| Fuse XRNP-35 |
|
|
|
|
| ||
Transformer SC9-35 |
|
|
|
|
| |||
Propose | Left (right) contact | Left (right) contact | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | |||
Scheme number | 16 | 17 | 18 | 19 | 20 | ||
Main circuit scheme diagram | | | | | ![]()
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 | 1~3 |
| 1~3 | 1~3 | 4~6 | |
| Voltage transformer JDJ9-35 |
|
|
|
|
| |
| Lightning arrester HY5WZ |
|
|
|
|
| |
| Grounding switchJN12-35 |
|
|
|
|
| |
| Live display |
|
|
|
|
| |
| Fuse XRNP-35 |
|
|
|
|
| |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Cable incoming(outgoing) line | Left (right) contact | Left (right)contact | Left (right) contact | Left (right) contact | ||
Scheme number | 21 | 22 | 23 | 24 | 25 | ||
Main circuit scheme diagram |
|
|
|
|
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 |
| 1~3 | 1~3 |
| 1~3 | |
| Voltage transformer JDJ9-35 |
|
|
|
|
| |
| Lightning arrester HY5WZ |
|
|
|
|
| |
| Grounding switchJN12-35 | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | |
| Live display | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | 0 or 1to select | |
| Fuse XRNP-35 |
|
|
|
|
| |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Overhead incoming (outgoing) line | Cable incoming (outgoing) line | Cable incoming (outgoing) line | ||
Scheme number | 26 | 27 | 28 | 29 | 30 | ||
Main circuit scheme diagram |
|
|
|
|
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 | 1~3 | 1~3 | 1~3 | 1~3 | 1~3 | |
| Voltage transformer JDJ9-35 |
| 2 | 2 | 2 | 2 | |
| Lightning arrester HY5WZ |
|
|
|
|
| |
| Grounding switchJN12-35 | 0 or 1to select |
|
|
|
| |
| Live display | 0 or 1to select |
|
|
|
| |
| Fuse XRNP-35 |
| 3 | 3 | 3 | 3 | |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Cable incoming (outgoing) line | Metering and Overhead incoming line | Metering and Overhead incoming line | Metering and Overhead incoming line | Metering and Overhead incoming line | ||
Scheme number | 31 | 32 | 33 | 34 | 35 | ||
Main circuit scheme diagram |
|
|
|
|
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 | 1~3 | 1~3 |
|
|
| |
| Voltage transformer JDJ9-35 | 2 | 2 | 1~3 | 1~3 | 1~3 | |
| Lightning arrester HY5WZ |
|
|
|
|
| |
| Grounding switchJN12-35 |
|
|
|
|
| |
| Live display |
|
|
|
|
| |
| Fuse XRNP-35 | 3 | 3 | 3 | 3 | 3 | |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | Metering and contact | Metering and contact | Voltage transformer | Voltage transformer and Cable incoming (outgoing) line | Voltage transformer and contact | ||
Scheme number | 36 | 37 | 38 | 39 | 40 | ||
Main circuit scheme diagram |
|
|
|
|
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 | 1~3 |
| 1~3 | 1~3 | 4~6 | |
| Voltage transformer JDJ9-35 |
|
|
|
|
| |
| Lightning arrester HY5WZ |
| 3 | 3 | 3 | 3 | |
| Grounding switchJN12-35 |
|
|
|
|
| |
| Live display |
|
|
|
|
| |
| Fuse XRNP-35 | 3 |
|
| 3 | 3 | |
Transformer SC9-35 |
|
|
|
|
| ||
Purpose | PT and Overhead incoming (contact) line | Lightning arrester | Lightning arrester and Cable incoming (outgoing) line | Lightning arrester and contact | Lightning arrester and Overhead incoming (contact) line | ||
Scheme number | 41 | 42 | 43 |
|
| ||
Main circuit scheme diagram |
|
|
|
|
| ||
| Vacuum circuit breaker ZN85-40.5 |
|
|
|
|
| |
| Current transformer LDJ5-35 |
|
|
|
|
| |
| Voltage transformer JDJ9-35 | 1~3 |
|
|
|
| |
| Lightning arrester HY5WZ | 3 |
|
|
|
| |
| Grounding switchJN12-35 |
|
|
|
|
| |
| Live display |
|
|
|
|
| |
| Fuse XRNP-35 | 3 |
|
|
|
| |
Transformer SC9-35 |
| 1 | 1 |
|
| ||
Purpose | Lightning arrester and contact(PT) |
| Transformer for substation |
| |||
The following technical data shall be provided when ordering:
1. Main circuit scheme number, purpose and main circuit scheme, layout plan and arrangement diagram of distribution room, etc;
2. Requirements f or control, measurement and protection functions of switchgear and requirements for other enclosed and automatic devices;
3. Model, specification and quantity of electrical components of switchgear;
4. If bus bridge connection is required between switchgear or into eel cabinet, specific requirements data such as rated flow of bus bridge, span of bus bridge and height from the ground shall be provided;
5. When the switchgear is used under special environmental conditions, it shall be described in detail when ordering;
6. Other special requirements shall be negotiated with the company.