HomeProductsPower transformer Power Oil Immersed Transformer

35KV Oil Immersed Transformer

Three-phase Double-winding with off-circuit Tap Changer
Rated voltage: 35KV
Rated capacity: 50-1600KVA、630-2500KVA、630-31500KVA
Propose: Power transmission and distribution system、industrial power supply、new energy power generation
Temperature: - 25℃~+40℃、Altitude≤1000m
Standards: IEC 60076
35KV  Oil Immersed Transformer - 华通大图
35KV  Oil Immersed Transformer - 华通大图2
35KV  Oil Immersed Transformer - 华通大图
35KV  Oil Immersed Transformer - 华通大图2
Application & Technical Parameters
Type Meaning

华通型号说明.png

Main technical parameters

50-1600KVA


Rated
     capacity (kVA)

Voltage ratio
     (kV)

Commichion
     Smbol

Loss values for S9 series transformer
     (kW)

Loss values for S10 series transtormer
     (kW)

loss values for S11 series transfomer
     (kW)

No-load
     current
     (%)

Impedance

(%)

Weight

Outline Dimension(mm)

Gauge
     (mm)

 

HV

 

LV

No-load Loss(kW)

load Loss(kW)

No-loadLoss(kW)

load Loss(kW)

No-load Loss(kW)

load Loss(kW)

Oil weight

Untankingweight

Total
     weight

L

W

H

50

 

 

35
       38.5
       ±5%
       或
       ±2x
       2.5%

 

 

 

0.4

 

 

 

Yyn0 Dyn11

0.21

1.21

0.19

1.15

0.17

1.15

2

 

 

 

6.5

275

 

740

1100

1000

1700

660

100

0.29

2.02

0.26

1.92

0.23

1.92

1.8

350

995

1100

1150

1750

660

125

0.34

2.38

0.31

2.26

0.27

2.26

1.7

430

1250

1100

1150

1800

660

160

0.36

2.83

0.32

2.69

0.29

2.69

1.6

450

1405

1160

1150

1860

660

200

0.43

3.33

0.39

3.16

0.34

3.16

1.5

495

1460

1230

1300

1950

660

250

0.51

3.96

0.46

3.76

0.41

3.76

1.4

520

1625

1250

1300

2000

660

315

0.61

4.77

0.55

4.53

0.49

4.53

1.4

590

1915

1400

1320

2070

820

400

0.73

5.76

0.66

5.47

0.58

5.47

1.3

680

2175

1510

1350

2150

820

500

0.86

6.93

0.77

6.58

0.69

6.58

1.2

760

2485

1620

1370

2240

820

630

1.04

8.28

0.94

7.87

0.83

7.87

1.1

830

2950

1750

1390

2330

820

800

1.23

9.9

1.11

9.41

0.98

9.41

1

880

3370

1900

1420

2400

820

1000

1.44

12.15

1.3

11.54

1.15

11.54

1

1005

4140

2165

1450

2485

820

1250

1.76

14.67

1.58

13.94

1.41

13.94

0.9

1160

4700

2230

1500

2600

1070

1600

2.12

17.55

1.91

16.67

1.7

16.67

0.8

1250

5570

2250

1650

2650

1070

630-2500KVA

Rated
     capacity (kVA)

Voltage ratio
     (kV)

Commichion
     Smbol

Loss values for S9 series transformer
     (kW)

Loss values for S10 series transtormer
     (kW)

loss values for S11 series transfomer
     (kW)

No-load
     current
     (%)

Impedance

(%)

Weight

Outline Dimension(mm)

Gauge
     (mm)

 

HV

 

LV

No-load Loss(kW)

load Loss(kW)

No-loadLoss(kW)

load Loss(kW)

No-load Loss(kW)

load Loss(kW)

Oil weight

Untankingweight

Total
     weight

L

W

H

630

35
     38.5
     ±5%
     或
     ±2x
     2.5%

 

6.3
       6.6
       10
       10.5
       11

 

 

Yd11

1.04

8.28

0.94

7.87

0.83

7.87

1.1

 

 

 

6.5

0.65

 

2.9

2100

1300

2300

820

800

1.23

9.9

1.11

9.4

0.98

9.4

1

0.7

3.2

2200

1350

2350

820

1000

1.44

12.15

1.3

11.54

1.15

11.54

1

0.85

3.5

2350

1450

2400

820

1250

1.76

14.67

1.58

13.94

1.41

13.94

0.9

1.01

3.84

2500

1600

2450

1070

1600

2.12

17.55

1.91

16.67

1.7

16.67

0.8

1.2

5

2600

1700

2500

1070

2000

2.72

19.35

2.45

18.38

2.18

18.38

0.7

1.28

6

2730

1800

2600

1070

2500

3.2

20.7

2.88

19.67

2.56

19.67

0.6

1.4

7

2870

1900

2700

1070

630-31500KVA

Rated
   Power     (kVA)

Voltage combination and tapping

                    range

Connection
     symbol

No-load Loss
     (kW)

load Loss
     (kW)

No-load
     Current
     (%)

Short-
     circuit
     Impedance
     (%)

HV  (kV)

Tapping

   Range of HV
          (%)

LV  (kV)

630

35

±2×2.5
     ±5

3.15
     6.3
     10.5

Yd11

0.830

7.86

0.65

6.5

800

0.980

9.40

0.65

1000

1.15

11.5

0.65

1250

1.40

13.9

0.55

1600

1.69

16.6

0.45

2000

2.17

18.3

0.45

2500

2.56

19.6

0.45

3150

35

    38.5

±2×2.5
     ±5

3.15
     6.3
     10.5

3.04

23.0

0.45

7.0

4000

3.61

27.3

0.45

5000

4.32

31.3

0.45

6300

5.24

35.0

0.45

8.0

8000

35 

    38.5

±2×2.5

3.15
     6.3
     10.5

YNd11

7.20

38.4

0.35

10000

8.70

45.3

0.35

12500

10.0

53.8

0.30

16000

12.1

65.8

0.30

20000

14.4

79.5

0.30

25000

17.0

94.0

0.25

10.0

31500

20.2

112

0.25


Sample data is for reference only. The company reserves the right to change the data, and to accept special orders.


ZM on-load tap-changer

1、rated voltage:35-220kV

2、rated frequency:50/60Hz

3、The maximum rated three-phase current capacity is from 300A to 2000A.

Technical Parameters


Item

Specification

Ⅲ300

Ⅲ500

Ⅲ600

I301

I501

I601

I800

I1200

I1500

1

Max.rated through current(A)

300

500

600

300

500

600

800

1200

1500

2

Rated frequency(Hz)

50 or  60

3

Phase & connect model

Three phase for Neutral point of Y connection

Single    phase  for  selectable winding connection

4

Max. rated step voltage(V)

3300

5

Rated step current(kVA)

1000

1400

1500

1000

1400

1500

2640

3100

3500

6

Short circuit current (kA)

Termal(3s)

6

8

8

6

8

8

16

24

24

Dynamic(peak)

15

20

20

15

20

20

40

60

60

7

Number of operating position

Linear regulation: 7、10、12、14、16、18、22、34 Reversing and coase and fine regulation: ±3~±17

 

8

Insulation level of tap changer (kV)

Rated Voltage

35

66

110

150

220

Max.working voltage

40.5

72.5

126

170

252

Power frequency withstand voltage(50Hz,1min)

85

140

230

325

460

Rated lightning impulse withstand voltage(1.2/50μs)

200

350

550

750

1050

9

Tap selector

4 grades of A, B, C and D according to the insulation level

10

Mechanical service life

Not less than 800,000

11

Electrical service life

Not less than 200,000

 

12

 

Oil compartment for diverter switch

Service pressure

3×104Pa

Leakage test

No leakage under 6×104Pa 24 hours

Over pressure protection

Blasting cap blast at (4~5)×105Pa

Protective relay

QJ4-25 oil flow speed set at 1.0m/s±10%

13

Oil drainage volume (L)

About 190~270

14

Oil filling volume (L)

About 125~190

15

Weight (kg)

About 240~350

16

Motor-driven unit

MAE/MA7B

basic wiring


华通尺寸图.png

Voltage gradiant of every part of regulating coil

image.png

image.png

External dimension diagram of ZM

image.png

Note: 

1.Step capacity = step voltage x load cuttent; Rated step capacity is the continuous permissible max.step capacity.

2.For single-phase tap changer formed by parallel of three-phase tap changer contacts; it is necaessary to take coil shounting of transformer into consideration. For ZMI800, there are two shunts. For ZMI1200 and I1500, there are three shunts.

3.The tap-changer of single phase liner regulating with 34 operating positions only have: I500A, I 800A, I1500A.